news
Home News Company News 500KVA Yuchai Diesel Generator Set Unload Container In Bangkok | Hospital Back Up Power

Table of Contents

    500KVA Yuchai Diesel Generator Set Unload Container In Bangkok | Hospital Back Up Power

    2025-01-15 16:51:59
    By Admin

    400kW Yuchai diesel generator set provides reliable backup power for a hospital in Bangkok. The hospital’s backup power system constitutes a multi-tiered power assurance framework, primarily comprising diesel generator sets serving as the main backup source, alongside UPS (Uninterruptible Power Supply) units that act as the final line of defense for critical equipment. 

    ⚙️ Core Equipment: Diesel Generator Sets
    These form the core of the hospital’s backup power system; they automatically start shortly after a utility power outage occurs, providing sustained electrical support to critical areas and equipment throughout the entire hospital.

    Configuration Requirements: According to the “Code for Electrical Design of Medical Buildings”, Class III hospitals are mandated to install emergency diesel generator sets, while Class II hospitals are “recommended” to do so. In actual practice, many hospitals adopt a “dual utility feed + diesel generator” configuration to ensure the highest level of power supply reliability.

    Key Performance Indicators:

    Startup Speed: Upon the loss of utility power, the diesel generator set must automatically start within 15 seconds and begin supplying power to the designated electrical loads.

    Continuous Operation Duration: For Class III hospitals, the fuel tank capacity must be sufficient to support the generator set’s continuous operation for a period exceeding 24 hours.

    Real-world Example: The Yulin Maternal and Child Health Hospital is currently procuring a 1005kVA diesel generator set. The specifications require automatic transfer within 15 seconds of a utility power failure; the onboard fuel storage must be capable of sustaining continuous power for at least 3 hours during a fire emergency, while also featuring a reserved interface to facilitate refueling for extended operation exceeding 24 hours.

    🛡️ The Final Line of Defense: UPS (Uninterruptible Power Supply)
    For equipment where any power interruption is absolutely impermissible—such as in operating rooms, ICUs (Intensive Care Units), neonatal wards, and medical refrigerators—relying solely on generator sets is insufficient. This is because there is an inherent, albeit brief, transition period between the generator’s startup and the stabilization of its power output (even though this process is required to be completed within 15 seconds). Consequently, a UPS (Uninterruptible Power Supply) is required to bridge this power “gap.”

    Core Function: To achieve a 0-millisecond transfer time, thereby ensuring absolute continuity of power supply and safeguarding precision medical equipment—as well as patient life support systems—against the adverse effects of power outages.

    Backup Duration: The energy storage capacity (batteries) of a UPS typically needs only to be sufficient to sustain power for a duration exceeding 15 minutes. These 15 minutes are intended to “bridge the gap” until the diesel generator successfully starts up and runs stably, thereby creating a seamless handover.

    500KVA YUCHAI DIESEL GENERATOR SET UY500GFS

    Standby Power(50HZ)

    440KW/550KVA

    Prime Power(50HZ)

    400KW/500KVA

     

    Generator Ratings

     

    Voltage

    HZ

    Phase

    P.F

    Prime

    Amps

    Standby Power 

     (KVA)

    Prime Power 

    (KVA)

    400/230V

    50

    3

    0.8

    792/720A

    550

    500

     

      Prime power (PRP): Prime power is available for an unlimited number of annual hours in available load application, in according with GB/T2820-97(EQVLso8528); A 10% overload capability is available for a period of 1 hour within a 12-hour period of operation.

     

      Standby power Rating (ESP): The standby power rating is application for supplying emergency power for the duration of a utility power interruption. No overload, utility parallel or negotiated outage operation capability is available at this rating.

     

    Sales Promises

     

    We provide a full line of brand new and high quality products. Each and every unit is strictly on load tested before delivery. Warranty is according to our standard conditions: 12 months or 1500 running hour’s, whichever occurs first. Service and parts are available from our factory or distribution in your location.

     

    ENGINE DATA

     

    Manufacturer /Model

    Yuchai YC6T660L-D20

    Air intake System

    Turbocharged intercooler

    Cylinder Arrangement

    6 in LINE

    Cooling system

    water cooled

    Displacement

    16.35L

    Bore and Stroke

    145*165(MM)

    Compression Ratio

    15:1

    Rated RPM

    1500rpm

    Prime power at rated RPM

    441KW

    Max standby Power at Rated RPM

    485KW

    Governor Type

    Electronic

    Start system

    DC24V electric start

    Rated fuel consumption

    192g/kw.h

    Oil capacity

    45L

     

    ALTERNATOR SPECIFICATION

    General data

    Compliance with GB755, BS5000, VDE0530, NEMAMG1-22, IED34-1, CSA22.2 and AS1359 standards.

    Alternator Data

     

    Manufacturer /Model

    Stamford technology alternator /5D

    Number of Phase

    three

    Number of Bearing

    one

    Power Factor

    0.8

    Protection Grade

    IP23

    Altitude

    ≤1000m

    Exciter Type

    Brush less, self-exciting

    Insulation Class, Temperature Rise

    H/H

    Telephone Influence Factor (TIF)

    < 50

    THF

    <2%

    Voltage Regulation, Steady State

    ≤1.5%

    Alternator Capacity

    500KVA

     

    Stamford alternator feature

    1. Temperature rise and motor starting performance comply with NEMA-MG21, UTE NFC51.111, VDE 0530, BS 4999, CSA standards

    2. Withstands 300% rated short circuit current for up to 10 seconds

    3. Persistent short circuit current will trip the downstream circuit breaker without damaging the generator

    4. Self-ventilating and drip-proof construction

    5. Windings are vacuum impregnated with antibacterial epoxy paint for high reliability and long life

    6. Excellent voltage waveform derived from 2/3 pitch stator and skewed rotor

    7. Fast response, permanent excitation

     

    Yuchai engine Design advantages:

    (1) Adopting the world’s advanced 4-valve structure and mid-mounted fuel injector, the oil and gas are more fully mixed.

    (2) Adopt international advanced electronic injection technology, high injection pressure, full combustion, high power density and light weight.

    (3) The mature supercharging and intercooling technology ensures sufficient air intake under various load conditions and wide economic fuel consumption area.

    (4) Reticulated rib structure cylinder block, alloy forged crankshaft, vermicular graphite cast iron cylinder head to ensure product quality.

    (5) The Yuchai engine is calibrated for plateau and alpine regions, and is suitable for use in high-altitude areas.

    (6) Yuchai’s entire series of engines purchased EFI technology, which is easy to start the engine, has a good response time for sudden addition and sudden reduction, and meets the national regulation T3 emission.

    (7) Plate type oil cooler, high heat exchange efficiency, the engine is not easy to be high temperature.

    (8) Cast oil pan, vermicular graphite cast iron cylinder head, alloy cylinder block, prolong engine life.

    (9) Integral forged steel crankshaft, light weight and high strength

    (10) There is only one exhaust main pipe, which is convenient for layout and installation, especially for indoor space.