Uleengen Medium Voltage 13.8KV 1500KVA Diesel Generator Set Passed FAT | air base KTA50-G12A
Els conjunts de generadors militars estan construïts amb estàndards que superen molt els conjunts de generadors comercials típics.
1. Military use generator sets Extreme Reliability & Uptime: Mission-critical operations depend on uninterrupted power. Redundancy and simple maintenance are vital.
2. Ruggedness & Durability: Must withstand severe shock, vibration, corrosion, sand, dust, rain, high altitude or temperature extremes (-40°C to +52°C is common).
3. Mobility & Deployability: Often skid-mounted, trailer-mounted, or integrated into shelters (ISO containers) for rapid air, sea, and land transport.
4. Potència de sortida i adaptabilitat de càrrega: els conjunts de generadors militars solen tenir capacitats de sortida d'alta potència, poden donar suport al funcionament de múltiples dispositius simultàniament i poden adaptar-se a càrregues instantànies altes.
5. baixa observabilitat: signatures tèrmiques, acústiques i electromagnètiques reduïdes per evitar la detecció.
6. silenci tàctic: tancaments acústics especials i dissenys d'escapament per reduir la petjada auditiva per a operacions ocultes.
7. Control d'interferències electromagnètiques (EMI): no ha d'interferir amb comunicacions sensibles i equips de radar.
8. Standardization & Compatibility: Adherence to military standards (MIL-STD) for connectors, voltages, and phases to ensure interoperability across all branches.

|
1500 KVA CUMMINS DIESEL GENERATOR SPECIFICATION |
|
|
Models |
UC1500GFC |
|
Standby Power(60HZ) |
1320KW / 1650KVA |
|
Prime Power(60HZ) |
1200KW / 1500KVA |
|
Generator Ratings |
|
Voltatge |
HZ |
Phase |
P.F |
Prime Amps |
Standby power (KVA) |
Prime power (KVA) |
|
13.8KV |
60 |
3 |
0.8 |
62.8A |
1650 |
1500 |
Prime power (PRP): Prime power is available for an unlimited number of annual hours in available load application, in according with GB/T2820-97(EQVLso8528); A 10% overload capability is available for a period of 1 hour within a 12-hour period of operation.
Standby power Rating (ESP): The standby power rating is application for supplying emergency power for the duration of a utility power interruption. No overload, utility parallel or negotiated outage operation capability is available at this rating.
|
Sales Promises |
We provide a full line of brand new and high quality products. Each and every unit is strictly on load test before delivery. Warranty is according to our standard conditions: 12 months or 1500 running hour’s, subject to the earlier one. Service and parts are available from our factory or distribution in your location.
|
DADES DEL MOTOR |
|
Manufacturer /Model |
Cummins / KTA50-G12A |
|
Air intake System |
Turbocharged and air-air inter cooler |
|
Cooling system |
water cooled |
|
Cylinder Arrangement |
16 cylinder V type |
|
Desplaçament |
50.3L |
|
Bore and Stroke |
159*159(MM) |
|
Compression Ratio |
13.9:1 |
|
Rated RPM |
1800rpm |
|
Prime power at rated RPM |
1347KW |
|
Max standby power at rated RPM |
1582KW |
|
Capacitat petroliera |
148-178L |
|
Governor |
electric |
|
Fuel consumption@100% load |
280L/hr |
|
Max intake resistance (KPa) |
6.23 |
|
Air intake (m3/h) |
5371 |
|
Max exhaust back pressure (KPa) |
6.8 |
|
Exhaust gas flow (m3/h) |
13374 |
|
Exhaust temp (℃) |
503 |
|
Cooling way |
Water Radiator & Fan |
|
Fan exhaust flow (m3/min) |
1700 |
|
Coolant capacity (L) |
430 |
|
Highest water temperature(℃) |
104 |
|
ALTERNATOR SPECIFICATION |
|
General data |
Compliance with GB755, BS5000, VDE0530, NEMAMG1-22, IED34-1, CSA22.2 and AS1359 standards.
|
Alternator Data |
|
Brand /Model |
EvoTec TH528B |
|
Number of Phase |
three |
|
Number of Bearing |
one |
|
Power Factor |
0.8 |
|
Protection Grade |
IP23 |
|
Altitude |
≤1000m |
|
Exciter Type |
Brush less, self-exciting |
|
Insulation Class, Temperature Rise |
H/H |
|
Freqüència |
60hz |