600kw 750kva Cummins Diesel Generator Synchronization Finished Commissioning In Malaysia
A 600 kW generator set supplies power to office buildings and commercial parks. In the event of a grid failure, it ensures the continued operation of critical facilities—such as elevators, lighting, fire safety systems, and security surveillance.
Despite the continuous advancement of new energy technologies, diesel generators maintain an absolute dominance in the market, commanding a 73.75% share due to their high reliability and fuel efficiency. With its mature technology and a nationwide maintenance network, the 600 kW diesel generator set currently stands as the most reliable and secure choice available.
600kw 750KVA Cummins diesel generator powered by Cummins engine KTA38-G2. Cummins diesel generator sets with the feature of good quality, stable performance and low fuel consumption, and are widely used in public utilities, industrial and mining enterprises, engineering construction, animal husbandry, communications and other fields.
A set of parallel system, so that when the mains power fails, the generator sets are required to supply power, the two generator sets are automatically paralleled to supply power to the load. When the load is less than 60% of the rated power of a single generator set (adjustable), the system will send a “reduce machine” signal, unload the standby input generator set and de-load the generator set and automatically stop. If the load is bigger than 80% (adjustable) of the rated capacity of a single generator set, the system will automatically issue an “increase generator command” to automatically start the standby generator set, and automatically parallelize after automatic synchronization, and automatically share the active load equally. The condition for parallel use is that the instantaneous voltage, frequency and phase of the two generators are the same.

|
750KVA CUMMINS DIESEL GENERATOR UC750GF |
|
|
Standby Power(50HZ) |
660KW/825KVA |
|
Prime Power(50HZ) |
600KW/750KVA |
|
Generator Ratings |
|
Voltage |
HZ |
Phase |
P.F |
Prime Amps |
Standby Power (KVA) |
Prime Power (KVA) |
|
380/220V |
50 |
3 |
0.8 |
1039 |
825 |
750 |
|
400/230V |
50 |
3 |
0.8 |
1083 |
825 |
750 |
|
415/240V |
50 |
3 |
0.8 |
1043 |
825 |
750 |
Prime power (PRP): Prime power is available for an unlimited number of annual hours in available load application, in according with GB/T2820-97(EQVLso8528); A 10% overload capability is available for a period of 1 hour within a 12-hour period of operation.
Standby power Rating (ESP): The standby power rating is application for supplying emergency power for the duration of a utility power interruption. No overload, utility parallel or negotiated outage operation capability is available at this rating.
|
ENGINE DATA |
|
Manufacturer /Model |
Cummins KTA38-G2 |
|
Air intake System |
Turbocharged and after-cooled |
|
Fuel System |
direct injection |
|
Cylinder Arrangement |
12V |
|
Displacement |
37.8L |
|
Bore and Stroke |
159*159(MM) |
|
Compression Ratio |
14.5:1 |
|
Rated RPM |
1500rpm |
|
Prime power at rated RPM |
664KW |
|
Max standby Power at Rated RPM |
731KW |
|
Governor Type |
electric |
|
Exhaust System |
|
Maximum Allowable Back Pressure – in kPa |
10 |
|
Exhaust Pipe Size Normally Acceptable in.(mm) |
6.0(152) |
|
Air Intake System |
|
Maximum Allowable Intake Air Restriction with Heavy Duty Air Cleaner/Clean Element – in. H2O( kPa ) |
15(3.73kpa) |
|
Minimum Allowable Dirt Holding Capacity with Heavy Duty Air Cleaner – g/cfm(g-L/s) |
25(53) |
|
Fuel System |
|
100%(Prime Power) Load |
213g/Kwh |
|
75%(Prime Power) Load |
218g/Kwh |
|
50%(Prime Power) Load |
230g/Kwh |
|
100%(Prime Power) Load |
159.2L/h |
|
Oil System |
|
Oil Consumption |
≤1.0g/KWhr |
|
Oil Pan Capacity (Option OP6023) High/Low – U.S. gal.(litre) |
30-23(114-87)
|
|
Rated Speed – PSI(kPa) |
43-70(297-483) |
|
Cooling System |
|
Coolant Capacity(only engine) |
118L |
|
Thermostat |
82-93℃ |
|
Max top tank Temperature |
104℃ |
|
ALTERNATOR SPECIFICATION |
|
General data |
Compliance with GB755, BS5000, VDE0530, NEMAMG1-22, IED34-1, CSA22.2 and AS1359 standards.
|
Alternator Data |
|
Manufacture /Type |
6B |
|
Number of Phase |
three |
|
Connecting Type |
3 Phase and 4 wire |
|
Number of Bearing |
one |
|
Power Factor |
0.8 |
|
Protection Grade |
IP23 |
|
Altitude |
≤1000m |
|
Exciter Type |
Brush less, self-exciting |
|
Insulation Class, Temperature Rise |
H/H |
|
THF |
<2% |
|
Voltage Regulation, Steady State |
≤1.5% |
|
Alternator Capacity |
750KVA |