Perkins Diesel Generators 80kva 50kva 30kva 20kva Shipped to Chad to Power the Telecommunications station
24 sets Silent Perkins diesel generators delivered from UleenGen
In today’s society, which relies heavily on electric power, diesel generator sets play an indispensable role—whether in ensuring the uninterrupted operation of data centers, communication station, supporting continuous mining operations, or serving as emergency backup power for critical facilities such as hospitals and airports. Among global engine brands, Perkins undoubtedly stands out as a shining star. Since its inception in 1932, Perkins has earned the trust of users worldwide, thanks to its deep technical heritage, exceptional fuel economy, and unparalleled reliability.
For customers planning to order a Perkins generator, this represents far more than a simple equipment purchase; it is a long-term investment critical to the future security and efficiency of their operations. our Client from Chad ordered 24 units Perkins generators for the telecommunication station, mainly include 80KVA, 50KVA, 30KVA and 20KVA. This marks a significant milestone in our expansion into the Chadian market.
The Silent Force Connecting Africa: How Perkins Generator Sets Fortify the “Lifeline” of Telecom Networks
Amidst the wave of digital transformation sweeping across Africa, the number of mobile communication subscribers in Sub-Saharan Africa has surpassed one billion. However, the widespread weakness of power grid infrastructure remains the single greatest bottleneck hindering the industry’s growth. When the grid experiences frequent fluctuations or fails completely, Perkins generator sets—distinguished by their exceptional reliability and technical innovation—quietly step in to sustain the continent’s vital communication arteries.
Absolute Reliability: Countering an Unstable Grid
The primary challenge facing African telecom operators is the extreme instability of the power grid. Frequent power outages, voltage dips, and surges not only risk damaging sensitive base station equipment but also directly result in signal interruptions and a degraded user experience. For both densely populated urban centers and remote rural areas, such interruptions translate into a complete standstill of economic activity.
Against this backdrop, generator sets powered by Perkins engines have become standard equipment for base stations. In Senegal, for instance, we supplied the country’s largest telecom operator with 22 kVA units powered by Perkins 404D-22G engines. These units are capable of seamlessly taking over power supply in the event of a grid failure, ensuring continuous operation for up to seven days without requiring any manual intervention. This “plug-and-play” backup power mechanism grants operators invaluable time to dispatch maintenance teams, thereby ensuring that user communications remain “always connected.”
Engineering Innovation: Extreme Adaptability—”Built for Africa”
The African environment imposes extremely harsh conditions on mechanical equipment; high temperatures, wind-blown sand, high humidity, and the logistical challenges inherent to remote regions all place exceptionally high demands on machinery. While standard industrial equipment often sees its service life drastically shortened in such environments, Perkins generator sets are engineered from the ground up with these extreme conditions in mind.
To combat high-temperature environments, Perkins and its partners have undertaken extensive optimizations of their cooling and air filtration systems. For example, in a telecom project in Saudi Arabia, the Perkins-powered generator sets we delivered were designed to operate as “prime power” sources—capable of functioning continuously and stably in ambient temperatures exceeding 50 degrees Celsius. This exceptional heat resistance ensures that base stations continue to transmit signals without interruption, even amidst the scorching heatwaves of Africa’s dry seasons. Furthermore, addressing the challenges associated with maintaining remote base stations, the Perkins 400 Series engine is renowned for its compact design and exceptionally long maintenance intervals. In a telecommunications project in Thailand—an operational environment similar to that of Africa—generator sets powered by Perkins engines garnered high acclaim from clients for their fuel efficiency, compact footprint, low noise levels, and extended maintenance and operational cycles. These very characteristics have also been proven across the African continent to be pivotal in enhancing the Return on Assets (ROA) for telecommunications operators.
From “Standby” to “Prime Power”: A Catalyst for Hybrid Energy Solutions
As the African telecommunications sector becomes increasingly sensitive to Operational Expenditure (OPEX), the traditional model of relying solely on diesel for power supply is undergoing a fundamental transformation. Today, Perkins generator sets are no longer merely backups for the utility grid; instead, they have evolved into core components of intelligent hybrid microgrids integrating solar PV, energy storage, and diesel power.
In Africa—a region blessed with abundant sunshine—solar panels can power base stations and recharge battery banks during the day. At night, or during prolonged periods of overcast and rainy weather, the Perkins generator sets automatically kick in once the battery reserves are depleted. This hybrid approach significantly reduces diesel consumption. Moreover, the Variable Speed
Perkins diesel generators specification
| Model de generador | 50 hz | Motor dièsel | Alternador | Mida general (mm) | Gross Weight (kg) | ||||||
| Power (kW) | Power (kVA) | Models | Rated Power (kW) | Número de cilindres | Forat xStroke (mm) | Desplaçament (L) | Rated Fuel Consumption (L/h) | Models | |||
| UP10GF | 8 | 10 | 403A-11G1 | 9 | 3.L | 77×81 | 1.131 | 1.9 | S0L1-H1 | resolucions 1580x810x930 | 500 |
| UP13GF | 10 | 13 | 403A-15G1 | 12 | 3.L | 84×90 | 1.496 | 2.4 | S0L1-L1 | resolucions 1580x810x930 | 520 |
| UP20GF | 16 | 20 | 404A-22G1 | 18 | 4.L | 84×100 | 2.216 | 3.8 | S0L2-G1 | resolucions 1580x810x990 | 540 |
| UP25GF | 20 | 25 | 404D-22TG | 25 | 4.L | 84×100 | 2.216 | 4.7 | S0L2-M1 | resolucions 1580x810x990 | 540 |
| UP30GF | 24 | 30 | 1103A-33G | 28 | 3.L | 105×127 | 3.3 | 5.6 | S0L2-P1 | Dimensions: 1580x810x1165 | 660 |
| UP40GF | 32 | 40 | 1103A-33TG1 | 42 | 3.L | 105×127 | 3.3 | 7.5 | S1L2-K1 | Dimensions: 1595x810x1150 | 730 |
| UP45GF | 36 | 45 | 1103A-33TG1 | 42 | 3.L | 105×127 | 3.3 | 8.4 | S1L2-N1 | Dimensions: 1595x810x1150 | 730 |
| UP60GF | 48 | 60 | 1104A-44TG1 | 58 | 4.L | 105×127 | 4.4 | 11.2 | S1L2-Y1 | Dimensions: 1580x810x1166 | 780 |
| UP80GF | 64 | 80 | 1104A-44TG2 | 72 | 4.L | 105×127 | 4.4 | 14.9 | UCI224G | Dimensions: 1760x810x1165 | 800 |
| UP100GF | 80 | 100 | 1104C-44TAG2 (en anglès) | 90 | 6.L | 105×127 | 4.41 | 18.7 | UCI274C | Dimensions: 2240x960x1315 | 1030 |
Anterior: Cap